Sabo Systems Pvt. Ltd.
Nishatganj, Lucknow, Uttar Pradesh
Send E-mail
Send SMS
Home»Our Products»

SURGE PROTECTION DEVICE FOR LV POWER

We are a leading supplier of a wide range of Surge Protection Devices. These products are manufactured by SALTEK in Czech Republic using superior quality raw material keeping in mind the needs and requirements of our clients. The products that we offer to our clients are made under the strict supervision and guidance of our quality check experts. These products are made as per the set international norms. The products that we offer in this category are Power Line Combined Lightning & Surge Arrestor. These products are mainly used to protect all electrical and electronic devices such as CNC machines, telecom equipments, signalling equipments, VFD's, computer, refrigerator, computers, music system, etc.


REQUEST CALLBACK
Get Best Quote

Approx. Rs 6,000  / Piece Get Latest Price

Provided by us is a commendable range of Power Line Combined Lightning & Surge Arrester to our respected patrons. Offered range of products are extensively used in various industries and sectors to protect electronic devices from sudden voltage fluctuations and switching processes. These Surge arrester for power equipments are manufactured by making use of superior grade raw material at the vendors base in compliance with the industry laid parameters.

 

Applications:

 

  • Switch mode power supply (SMPS)
  • Integrated power supply (IPS)
  • Distribution board /sub distribution board
  • Input power supply to load to be protected like after fuse in house/flat etc
  • CNC machines
  • Automatic frequency track circuit
  • Point machine
  • Drives/VFD (variable frequency drives)
  • Axle counter
  • Power line combined lightning & surge arrester
  • On line UPS
  • Servo stabilizers
  • LC gates
  • Battery chargers
  • Access control System
  • Reservation centers/data control centers/servers
  • Printing machine

Additional Information:
  • Item Code: DT50-350
  • Minimum Order Quantity: 10 Piece
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Production Capacity: 1000 PER MONTH
  • Delivery Time: 2-6 Weeks
  • Packaging Details: Carton
Yes! I am Interested
View PDF
REQUEST CALLBACK
Get Best Quote

Approx. Rs 2,200  / Piece Get Latest Price

SLP-PV1000 V/Y SLP-PV1000 V/Y S SPD type 2 – surge arrester for photovoltaic systems Replaceable varistor module, visual fault signalling. Surge arrester is specially designed for installation in the direct current circuits of photovoltaic/solar systems. Optional remote status signalling (S). Maximum continuous operating voltage for PV application: UCPV ≥ 1,2× UOC STC   Technical data SLP-PV1000 V/Y S SLP-PV1200 V/Y S Maximum continuous operating voltage (1/2→3) UCPV 1020 V DC 1200 V DC Nominal discharge current (8/20 μs) In 30 kA In 15 kA 15 kA Max. discharge current (8/20 μs) Imax 30 kA 30 kA Voltage protection level Up 4,0 kA 4,2 kA Short-circuit withstand ISCWPV 125,A DC 125,A DC Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C ... + 80 °C – 40 °C ... + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected conductors Solid min/max Stranded min/max   ISO: 1/50 mm2 ; AWG: 17/1 ISO: 1/35 mm2 ; AWG: 17/2   ISO: 1/50 mm2 ; AWG: 17/1 ISO: 1/35 mm2 ; AWG: 17/2 Stripping length of the supply conductor 14 mm 14 mm Tightening torque max. 4 Nm max. 4 Nm Fault indication red indication field red indication field Meets the requirements prEN 50539-11:2010 prEN 50539-11:2010
Additional Information:
  • Item Code: SLP-PV-1000V
  • Minimum Order Quantity: 05 Piece
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

3 Phase Combined Class B & Class C lightning and surge protection device.

FLP-B+C MAXI VS/3+1

SPD Type 1 and type 2-combined arrester type 1 and 2

Highly efficient varistor lightning current arrester to be installed In low-voltage distributions at the boundary of LPZ Oa-LPZ 1 Zones and higher,to prevent overvoltage effects induced During direct or indirect lightning strikes.it is particularly. Suitable for residential houses and small buildings with A low-voltage cable terminal or for secondary switchboards In large building.

1- Visual fault signaling

2- Remote status signaling (S).

Advantages: No usage of separate Class C surge protection device.

To be installed in main LV panels, distribution board, sub distribution board or after meter, in parallel to the load. Very high degree of protection as no need of separate Class C surge protection device required.

Technical data

L-N

N-PE

Nominal voltage Un

230 V AC

--------

Maximum operating voltage Uc

260 V AC

255 V AC

Nominal discharge current (8/20 μs)/pole In

30 kA

100 kA

Maximum discharge current (8/20 μs) Imax

60 kA

100 kA

Lighting impulse current (10/350 μs)/pole Iimp

25 kA

100 kA

Voltage protection level Up

1,5 kV

1,5 kV

Response time ta

100 ns

100 ns

Ability to independently switch off the following current Ifi

no following current

100 A

Short-circuit proof at maximum overcurrent protection

50 kArms

-----------

Maximum overcurrent protection

250 A gL/gG

-----------

Maximum overcurrent protection for serial connection

125 A gL/gG

-----------




For Catalouge, Kindly check Attachment.

Additional Information:
  • Item Code: FLPBCMAXIV3-1
  • Minimum Order Quantity: 05 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
Save time! Get a Best Deal

*Your information is safe with us.

REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Lighting Current Arresters

FLP-B+C MAXI VS

SPD type 1 - combined arrester type 1 and 2 Dimension drawing Basic circuit diagram

Surge protector devices (SPD) of class B+C serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct - and indirect lightning strikes. The FLP-B+C MAXI VS SPD is built in a single block. Module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 sec pulse) with high energy varistors block. This module guarantee no follow-on current, very low leakage current (A range) and very low residual voltage. The form a part of the protection of buildings and their accessories in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones. reliable arrester disconnection during overload or damaging of the protective module by thermal and dynamical varistor disconnection optical fault indication - changing color of the signaling flag from green to red

low voltage Up

housing material according to UL 94 V0

Technical data

FLP-B+C MAXI VS

Nominal voltage Un

230 V AC

Maximum operating voltage Uc

260 V AC

Nominal discharge current (8/20 s) In

30 kA

Lightning impulse current (10/350 s) Iimp

25 kA

Maximum discharge current (8/20 s) Imax

60 kA

Voltage protection level Up

1,5 kA

Response time ta

100 ns

Ability to independently switch off the following current Ifi

no following current

Short-circuit proof at maximum overcurrent protection

50 kArms

Maximum overcurrent protection

250 A gL/gG

Maximum overcurrent protection for serial connection

125 A gL/gG

Degree of protection

IP 20

Range of operating temperatures

- 40 DegreeC + 80 DegreeC

Mounting on

DIN rail 35 mm

Cross-section of connected conductors

Solid min/max

Stranded min/max

ISO 10/50 mm2 ; AWG 7/1

ISO 10/35 mm2 ; AWG 7/2

For Catalouge,kindly check Attachment.


Additional Information:
  • Item Code: FLPBCMAXIVS
  • Minimum Order Quantity: 05 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Lightning Current Arresters FLP-A50N VS SPD type 1 - lightning current arrester N-PE module, replaceable module To be installed in low-voltage distributions at the boundary of LPZ 0A-LPZ 1 zones and higher to prevent overvoltage effects induced during direct or indirect lightning strikes for the connection of SPD type 1 in the mode 1+1. Technical data FLP-A50N VS Nominal voltage Un ---------- Maximum operating voltage Uc 255 V AC Nominal discharge current (8/20 s) In 50 kA Maximum discharge current (8/20 s) Imax 100 kA Lightning impulse current (10/350 s) Iimp 50 kA Voltage protection level Up 1,5 kV Response time ta 100 ns Ability to independently switch off the following current Ifi 100 A Short-circuit proof at maximum overcurrent protection ------------- Maximum overcurrent protection ------------- Degree of protection IP 20 Range of operating temperatures - 40 DegreeC + 80 DegreeC Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max Stranded min/max ISO 10/50 mm2 ; AWG 7/1 ISO 10/35 mm2 ; AWG 7/2 Stripping length of the supply conductor 11 mm Tightening torque max. 4 Nm Visual fault indication No Remote indication * potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC For Catalouge,Kindly check Attachment.
Additional Information:
  • Item Code: FLPA50NVS
  • Minimum Order Quantity: 05 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Lightning Current Arresters

FLP-A100N VS

SPD type 1 – lightning current arrester N-PE module, replaceable module To be installed in low-voltage distributions at the boundary of LPZ 0A and LPZ 1 zones to prevent overvoltage effects induced during direct or indirect lightning strikes for the connection of SPD type 1 in the mode 3+1.

Technical data

FLP-A100N VS

Nominal voltage Un

-------

Maximum operating voltage Uc

255 V AC

Nominal discharge current (8/20 μs)/pole In

100 kA

Maximum discharge current (8/20 μs) Imax

100 kA

Lighting impulse current (10/350 μs)/pole Iimp

100 kA

Voltage protection level Up

1,5 kV

Response time ta

100 ns

Ability to independently switch off the following current Ifi

100 A

Short-circuit proof at maximum overcurrent protection

--------

Maximum overcurrent protection

--------

Degree of protection

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

Cross-section of connected conductors

Solid min/max

Stranded min/max

 

ISO: 10/50 mm2 ; AWG: 7/1

ISO: 10/35 mm2 ; AWG: 7/2

Stripping length of the supply conductor

11 mm

Tightening torque

max. 4 Nm

Meets the requirements of standard

EN 61643-11 + A11T1T2

Ordering number

8595090535744

 

 

 

* Remote signaling of N-PE module available on request.
For Catalouge,Kindly check Attachment.


Additional Information:
  • Item Code: FLPA100NVS
  • Minimum Order Quantity: 05 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
Save time! Get a Best Deal

*Your information is safe with us.

REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

 

Surge Arresters

DA-275 V/3+1

DA-275 V/3S+1

SPD type 3 – surge arrester

Replaceable module, visual fault signaling

Combination of 3-pole varistor surge protection and an encapsulated spark gap connected in the mode 3+1. To be installed in low-voltage distributions at the boundary of LPZ 2 and LPZ 3 zones to protect distributions and equipment against overvoltage effects induced during a lightning strike and to

prevent switching overvoltage.Optional remote status signalling (S).

 

 

Technical data

L-N

N-PE

Nominal voltage Un

230 V AC

------

Maximum operating voltage Uc

275 V AC

255 V AC

Nominal discharge current (8/20 μs)/pole In

30 kA

20 kA

Maximum discharge current (8/20 μs)/pole Imax

60 kA

40 kA

Lighting impulse current (10/350 μs)/pole Iimp

8 kA

25 kA

Voltage protection level Up

1,2 kV

1,5 kV

Response time ta

25 ns

100 ns

Ability to independently switch off the following current Ifi

no following current

100 A

Short-circuit proof at maximum overcurrent protection

35 kArms

--------

Maximum overcurrent protection

160 A gL/gG

--------

Degree of protection

IP 20

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

DIN rail 35 mm

Cross-section of connected conductors

Solid min/max

Stranded min/max

 

ISO: 1/50 mm2 ; AWG: 17/1

ISO: 1/35 mm2 ; AWG: 17/2

 

ISO: 1/50 mm2 ; AWG: 17/1

ISO: 1/35 mm2 ; AWG: 17/2

Stripping length of the supply conductor

14 mm

14 mm

For Catalouge,Kindly Check Attachment.


Additional Information:
  • Item Code: DA-275V
  • Minimum Order Quantity: 10 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Surge Arresters

DA-075 DJ

DA-130 DJ

DA-275 DJ

SPD type 3 – surge arrester Visual fault signaling

Surge protection designed to protect all types of electric and electronic equipment connected to a low-voltage distribution against pulse overvoltage.

Technical data

DA-075 DJ

DA-130 DJ

DA-275 DJ

Nominal voltage Un

-------

110 V AC

230 V AC

Maximum operating voltage Uc

75 V AC

130 V AC

275 V AC

Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In

2 kA, 2 kA, 4 kA

2,5 kA, 2,5 kA, 5 kA

3 kA, 3 kA, 5 kA

Test voltage L-N, L(N)-PE, L+N-PE Uoc

4 kV, 4 kV, 8 kV

5 kV, 5 kV, 10 kV

6 kV, 6 kV, 10 kV

Voltage protection level L-N, L(N)-PE Up

0,4 kV, 1,2 kV

0,6 kV, 1,5 kV

1,2 kV, 1,6 kV

Response time L-N, L(N)-PE ta

25 ns, 100 ns

25 ns, 100 ns

25 ns, 100 ns

Short-circuit proof at maximum overcurrent protection

6 kA rms

6 kA rms

6 kA rms

Maximum overcurrent protection

16 A gL/gG; C 16 A

16 A gL/gG; C 16 A

16 A gL/gG; C 16 A

Degree of protection

IP 20

IP 20

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

– 40 °C … + 80 °C

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

DIN rail 35 mm

DIN rail 35 mm

Cross-section of connected conductors

 

Solid max

Stranded max

 

ISO: 6 mm2 ; AWG: 10

ISO: 4 mm2 ; AWG: 11

 

ISO: 6 mm2 ; AWG: 10

ISO: 4 mm2 ; AWG: 11

 

ISO: 6 mm2 ; AWG: 10

ISO: 4 mm2 ; AWG: 11

 

For Catalouge,Kindly Check Attachment.


Additional Information:
  • Item Code: DA075DJ
  • Minimum Order Quantity: 10 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Surge Arresters

DA-275 BFG

SPD type 3 – surge arrester with RFI filter in a metal bushing Visual fault signaling, earth terminal,class I.

Surge protection with an integrated RFI filter designed to protect M&C, ESS, EFS, etc. control systems against pulse overvoltage and RF disturbance.

 

Technical data

DA-275 BFG

Nominal voltage Un

230 V AC

Maximum operating voltage Uc

275 V AC

Nominal load current IL

16 A

Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In

3 kA, 3 kA, 5 kA

Test voltage L-N, L(N)-PE, L+N-PE Uoc

6 kV, 6 kV, 10 kV

Voltage protection level L-N, L(N)-PE Up

1,2 kV, 1,5 kV

Response time L-N, L(N)-PE ta

25 ns, 100 ns

Maximum overcurrent protection

16 A gL/gG nebo C16 A

Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical

30 dB

Degree of protection

IP 20

Range of operating temperatures

-40 °C … +80 °C

Mounting on

DIN rail 35 mm, surface on the desk

Cross-section of connected conductors

Solid max

Stranded max

 

ISO: 2,5 mm2 ; AWG: 13

ISO: 2,5 mm2 ; AWG: 13

Tightening torque

max. 0,6 Nm

Fault indication

red indicator

Remote indication

no

Meets the requirements of standard

EN 61643-11 + A11T3

Ordering number

8595090506294


Additional Information:
  • Item Code: DA275BGF
  • Minimum Order Quantity: 10 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
Save time! Get a Best Deal

*Your information is safe with us.

REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

 

Surge Arresters

DA-275 DF 10 S

DA-275 DF 16 S

SPD type 3 – surge arrester with RFI filter

Remote fault signaling

Surge protection with an integrated RFI filter designed to protect M&C, ESS, EFS, etc. control systems against pulse overvoltage and RF disturbance.

 

Technical data

DA-275 DF10 S

DA-275 DF16 S

Nominal voltage Un

230 V AC

230 V AC

Maximum operating voltage Uc

275 V AC

275 V AC

Nominal load current IL

10 A

16 A

Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In

3 kA, 3 kA, 5 kA

3 kA, 3 kA, 5 kA

Test voltage L-N, L(N)-PE, L+N-PE Uoc

6 kV, 6 kV, 10 kV

6 kV, 6 kV, 10 kV

Voltage protection level L-N, L(N)-PE Up

1,2 kV, 1,5 kV

1,2 kV, 1,5 kV

Response time L-N, L(N)-PE ta

25 ns, 100 ns

25 ns, 100 ns

Maximum overcurrent protection

10 A gL/gG nebo C10 A

16 A gL/gG nebo C16 A

Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical

30 dB

30 dB

Degree of protection

IP 20

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

DIN rail 35 mm

Cross-section of connected conductors

Solid max

Stranded max

 

ISO: 4 mm2 ; AWG: 11

ISO: 2,5 mm2 ; AWG: 13

 

ISO: 4 mm2 ; AWG: 11

ISO: 2,5 mm2 ; AWG: 13

Tightening torque

max. 0,6 Nm

max. 0,6 Nm

For Catalouge,Kindly check Attachment.


Additional Information:
  • Item Code: DA275DF10S
  • Minimum Order Quantity: 10 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Surge Arresters

DA-275 DF 25

SPD type 3 – surge arrester with RFI filter Visual fault signaling Surge protection with an integrated RFI filter designed to protect M&C, ESS, EFS, etc. control systems against pulse overvoltage and RF disturbance.

Technical data

DA-275 DF25

Nominal voltage Un

230 V AC

Maximum operating voltage Uc

275 V AC

Nominal load current IL

25 A

Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In

3 kA, 3 kA, 5 kA

Test voltage L-N, L(N)-PE, L+N-PE Uoc

6 kV, 6 kV, 10 kV

Voltage protection level L-N, L(N)-PE Up

1,2 kV, 1,5 kV

Response time L-N, L(N)-PE ta

25 ns, 100 ns

Maximum overcurrent protection

25 A gL/gG nebo C25 A

Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical

30 dB

Degree of protection

IP 20

Range of operating temperatures

–40 °C … +80 °C

Mounting on

DIN rail 35 mm

Cross-section of connected conductors

Solid max

Stranded max

 

ISO: 1/50 mm2 ; AWG: 17/1

ISO: 1/35 mm2 ; AWG: 17/2

Tightening torque

max. 4 Nm

Fault indication

red indicator

Meets the requirements of standard

EN 61643-11 + A11T3

Ordering number

8595090537328


Additional Information:
  • Item Code: DA275DF25
  • Minimum Order Quantity: 05 Pieces
  • Port of Dispatch: INDIA
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Lightning Current Arresters

FLP-12,5 V

FLP-12,5 VS

SPD type 1 and type 2 – lightning current arrester

Replaceable varistor module, visual fault signaling Varistor lightning current arrester to be installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage.Optional remote status signalling (S).

Technical data

FLP-12,5 V

Nominal voltage Un

230 V AC

Maximum operating voltage Uc

275 V AC / 350 V DC

Nominal discharge current (8/20 μs) In

30 kA

Maximal discharge current Imax

60 kA

Lightning impulse current (10/350 μs) Iimp

12,5 kA

Voltage protection level Up

1,2 kV

Response time ta

25 ns

Short-circuit proof at maximum overcurrent protection

35 kArms

Maximum overcurrent protection

160 A gL/gG

Degree of protection

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

Cross-section of connected conductors

Solid min/max

Stranded min/max

 

ISO: 1/50 mm2 ; AWG: 17/1

ISO: 1/35 mm2 ; AWG: 17/2

Stripping length of the supply conductor

14 mm

Tightening torque

max. 4 Nm

Fault indication

red indication field

Remote indication – S design

potential-free change-over contact

Remote indication contacts

250 V / 0,5 A AC, 250 V / 0,1 A DC

Cross-section of remote indication conductors

max. 1,5 mm2

Meets the requirements of standard

EN 61643-11 + A11T1T2

Ordering number

FLP-12,5 V

FLP-12,5 VS

 

8595090534211

8595090534228


Additional Information:
  • Item Code: FLP125V
  • Minimum Order Quantity: 05 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
Save time! Get a Best Deal

*Your information is safe with us.

REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

 

Lightning Current Arresters

FLP-12,5 V/3+1

FLP-12,5 V/3S+1

SPD type 1 and type 2 – lightning current arrester

Replaceable varistor module, visual fault signaling 3-pole varistor lightning current arrester to be installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

Technical data

L-N

N-PE

Nominal voltage Un

230 V AC

----------

Maximum operating voltage Uc

275 V AC

255 V AC

Nominal discharge current (8/20 μs) In

30 kA

50 kA

Maximal discharge current (8/20 μs) Imax

60 kA

100 kA

Lightning impulse current (10/350 μs) Iimp

12,5 kA

50 kA

Voltage protection level Up

1,2 kV

1,5 kV

Response time ta

25 ns

100 ns

Ability independently switch off the following current Ifi

no following current

100 A

Short-circuit proof at maximum overcurrent protection

35 kArms

---------

Maximum overcurrent protection

160 A gL/gG

---------

Degree of protection

IP 20

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

DIN rail 35 mm

Cross-section of connected conductors

Solid min/max

Stranded min/max

 

ISO: 1/50 mm2 ; AWG: 17/1

ISO: 1/35 mm2 ; AWG: 17/2

 

ISO: 1/50 mm2 ; AWG: 17/1

ISO: 1/35 mm2 ; AWG: 17/2

Stripping length of the supply conductor

14 mm

14 mm

Tightening torque

max. 4 Nm

max. 4 Nm

For Catalouge,Kindly check Attachment.


Additional Information:
  • Item Code: FLP125V31
  • Minimum Order Quantity: 10 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Lightning Current Arresters

FLP-275 V

FLP-275 VS

SPD type 1 and type 2

Replaceable varistor module, visual fault signaling Varistor lightning current arrester to be installed in low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

 

Technical data

FLP-275 V

Nominal voltage Un

230 V AC

Maximum operating voltage Uc

275 V AC / 350 V DC

Nominal discharge current (8/20 μs) In

30 kA

Maximum discharge current Imax

60 kA

Lightning impulse current (10/350 μs) Iimp

8 kA

Voltage protection level Up

1,2 kV

Response time ta

25 ns

Short-circuit proof at maximum overcurrent protection

35 kArms

Maximum overcurrent protection

160 A gL/gG

Degree of protection

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

Cross-section of connected conductors

Solid min/max

Stranded min/max

 

ISO: 1/50 mm2 ; AWG: 17/1

ISO: 1/35 mm2 ; AWG: 17/2

Stripping length of the supply conductor

14 mm

Tightening torque

max. 4 Nm

Fault indication

red indication field

Remote indication – S design

potential-free change-over contact

Remote indication contacts

250 V / 0,5 A AC, 250 V / 0,1 A DC

Cross-section of remote indication conductors

max. 1,5 mm2

Meets the requirements of standard

EN 61643-11 + A11T1T2

Ordering number

FLP-275 V

FLP-275 VS

 

8595090516200

8595090516217


Additional Information:
  • Item Code: FLP275V
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

 

Lightning Current Arresters

FLP-275 V/3+1

FLP-275 V/3S+1

SPD type 1 and type 2

Replaceable module, visual fault signaling

Combination of 3-pole varistor surge protection and an encapsulated spark gap connected in the mode 3+1. To be installed in low-voltage distributions at the boundary of LPZ 0B and LPZ 1 zones to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to

prevent switching overvoltage. Optional remote status signalling (S).

 

Technical data

L-N

N-PE

Nominal voltage Un

230 V AC

------

Maximum operating voltage Uc

275 V AC

255 V AC

Nominal discharge current (8/20 μs)/pole In

30 kA

20 kA

Maximum discharge current (8/20 μs)/pole Imax

60 kA

40 kA

Lighting impulse current (10/350 μs)/pole Iimp

8 kA

25 kA

Voltage protection level Up

1,2 kV

1,5 kV

Response time ta

25 ns

100 ns

Ability to independently switch off the following current Ifi

no following current

100 A

Short-circuit proof at maximum overcurrent protection

35 kArms

--------

Maximum overcurrent protection

160 A gL/gG

--------

Degree of protection

IP 20

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

DIN rail 35 mm

Cross-section of connected conductors

Solid min/max

Stranded min/max

 

ISO: 1/50 mm2 ; AWG: 17/1

ISO: 1/35 mm2 ; AWG: 17/2

 

ISO: 1/50 mm2 ; AWG: 17/1

ISO: 1/35 mm2 ; AWG: 17/2

Stripping length of the supply conductor

14 mm

14 mm

Tightening torque

max. 4 Nm

max. 4 Nm

For Catalouge,Kindly check Attachment.


Additional Information:
  • Item Code: FLP275V3
  • Minimum Order Quantity: 10 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
Save time! Get a Best Deal

*Your information is safe with us.

REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

 

Surge Arresters

SLP-075 VB

SLP-130 VB

SLP-275 VB

SPD type 2 – surge arrester Replaceable module, visual fault signaling

Efficient varistor connected in series with an encapsulated spark gap. To be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones. Designed to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage in areas with higher storm activity or to protect measuring circuits as a 1st protection level. In idle state it has

very little leakage current, which remains stable for the duration of the service life; protective elements are not subject to ageing.

 

Technical data

SLP-075 VB

SLP-130 VB

SLP-275 VB

Nominal voltage Un

-------

110 V AC

230 V AC

Maximum operating voltage Uc

75 V AC / 100 V DC

130 V AC / 170 V DC

275 V AC / 350 V DC

Nominal discharge current (8/20 μs) In

15 kA

20 kA

20 kA

Maximum discharge current (8/20 μs) Imax

25 kA

25 kA

25 kA

Lighting impulse current (10/350 μs)

2,5 kA

2,5 kA

2,5 kA

Voltage protection level @ I = 5 kA (8/20 μs) Up

0,3 kV

0,5 kV

0,9 kV

Voltage protection level Up

0,6 kV

0,7 kV

1,2 kV

Response time ta

100 ns

100 ns

100 ns

Short-circuit proof at maximum overcurrent protection

35 kArms

35 kArms

35 kArms

Maximum overcurrent protection

125 A gL/gG

125 A gL/gG

125 A gL/gG

Degree of protection

IP 20

IP 20

IP 20

For Catalouge,Kindly check Attachment.


Additional Information:
  • Item Code: SLP275VB
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

 

Surge Arresters

SLP-275 V/3+1

SLP-275 V/3S+1

SPD type 2 – surge arrester

Replaceable module, visual fault signaling Combination of 3-pole varistor surge protection and an

encapsulated spark gap connected in the mode 3+1. To be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S).

Technical data

L-N

N-PE

Nominal voltage Un

230 V AC

------

Maximum operating voltage Uc

275 V AC

255 V AC

Nominal discharge current (8/20 μs)/pole In

20 kA

20 kA

Maximum discharge current (8/20 μs)/pole Imax

40 kA

------

Voltage protection level @ I = 5 kA (8/20 μs) Up

0,9 kV

------

Voltage protection level Up

1,2 kV

1,5 kV

Response time ta

25 ns

100 ns

Ability to independently switch off the following current Ifi

no following current

100 A

Short-circuit proof at maximum overcurrent protection

35 kArms

--------

Maximum overcurrent protection

160 A gL/gG

--------

Degree of protection

IP 20

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

DIN rail 35 mm

Cross-section of connected conductors

Solid min/max

Stranded min/max

 

ISO: 1/50 mm2 ; AWG: 17/1

ISO: 1/35 mm2 ; AWG: 17/2

 

ISO: 1/50 mm2 ; AWG: 17/1

ISO: 1/35 mm2 ; AWG: 17/2

For Catalouge,Kindly check Attachment.


Additional Information:
  • Item Code: SLP275V31
  • Minimum Order Quantity: 10 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

 

Surge Arresters

SLP-075 V

SLP-130 V

SLP-275 V

SLP-385 V

SLP-440 V

SLP-600 V

SPD type 2 – surge arrester

Replaceable varistor module,visual fault signaling Varistor surge protection to be

installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect the distributions and equipment against overvoltage effects induced during a lightning strike and to prevent switching overvoltage.

Technical data

SLP-075 V

SLP-130 V

SLP-275 V

SLP-385 V

SLP-440 V

SLP-600 V

Nominal voltage Un

------

110 V AC

230 V AC

---------

400 V AC

--------

Maximum operating voltage Uc

75 V AC / 100 V DC

130 V AC / 170 V DC

275 V AC / 350 V DC

385 V AC / 500 V DC

440 V AC / 585 V DC

600 V AC

Maximum operating voltage of varistor

-------

--------

----------

--------

--------

880 V AC

Nominal discharge current (8/20 μs) In

15 kA

15 kA

20 kA

20 kA

20 kA

15 kA

Maximum discharge current (8/20 μs) Imax

40 kA

40 kA

40 kA

40 kA

40 kA

40 kA

Voltage protection level @ I = 5 kA (8/20 μs) Up

0,3 kV

0,45 kV

0,9 kV

1,3 kV

1,5 kV

2,7 kV

For Catalouge,Kindly check Attachment.


Additional Information:
  • Item Code: SLP385V
  • Minimum Order Quantity: 10 Pieces
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
Save time! Get a Best Deal

*Your information is safe with us.

REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Lightning Current Arresters

FLP-SG50 V

FLP-SG50 VS

SPD type 1 – lightning current arrester Encapsulated high-performance spark gap with replaceable module, visual fault signaling To be installed in low-voltage distributions at the boundary of LPZ 0A and LPZ 1 zones to prevent overvoltage effects induced during direct or indirect lightning strikes in the most demanding applications in the heavy and chemicals industry, power stations, etc.Remote status signaling (S).

Technical data

FLP-SG50 VS

Nominal voltage Un

230 V AC

Maximum operating voltage Uc

255 V AC

Nominal discharge current (8/20 μs) In

50 kA

Lightning impulse current (10/350 μs) Iimp

50 kA

Voltage protection level Up

<2,5 kV

Response time ta

100 ns

Ability to independently switch off the following current Ifi

50 kA

Nominal short circuit current ISCCR

50 kArms

Maximum overcurrent protection

315 A gL/gG

Maximum overcurrent protection for serial connection

125 A gL/gG

TOV voltage UT

335 V/5 sec.

Degree of protection

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

Cross-section of connected conductors

Solid min/max

Stranded min/max

 

ISO: 2,5/50 mm2 ; AWG: 13/1

ISO: 2,5/35 mm2 ; AWG: 13/2

Visual fault indication

red indication field

Remote indication – S design

potential-free change-over contact

Remote indication contacts

250 V / 0,5 A AC, 250 V / 0,1 A DC

Cross-section of remote indication conductors

max. 1,5 mm2

Meets the requirements of standard

EN 61643-11:2012T1

Ordering number FLP-SG50 V

FLP-SG50 VS

8595090540533

8595090540540

Kindly check PDF Attachment for product catalogue.


Additional Information:
  • Item Code: FLP-SG50V
  • Minimum Order Quantity: 10 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Surge Arresters

Replaceable modules

Accessories

SALTEK SPD type 1–3 with a “V“ in the part number are made with replaceable modules. This enables simple withdrawal

of the module from its base to test the systems insulation, without the need to disconnect the device from the circuit.

Furthermore the new modules enable simple up-down orientation of the SPD, according to the incoming cables and also it

serve for fast and easy replacement in case of failure.

The replacement modules (marked “xxx V/0”) are identical to the ones used in original product.

The voltages used cannot be mixed because of the identical voltage key on the module and the corresponding base part.


Additional Information:
  • Item Code: SPD-CARTRIDGE
  • Minimum Order Quantity: 10 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Surge Arresters

DP-012

Surge arrester for low-voltage power supplies Visual fault signalling Designed to protect a line of equipment connected to distributions of DC and AC supply voltage. According to the concept of lightning protection zones, it is installed at the boundary of LPZ 1–LPZ 2 zones and higher.

Technical Data

DP-012

Location SPD

ST 2

Nominal voltage Un

12 V AC/DC

Maximum operating voltage Uc

28 V DC / 22 V AC

Nominal current IL

16 A

C2 nominal discharge current (8/20 μs) per line In

2 kA

C2 voltage protection level line - line at In UP

160 V

C2 voltage protection level line - PE at In Up

530 V

C3 voltage protection level line - line at 1 kV/μs In

2 kA, 2 kA

C3 voltage protection level line - PE at 1 kV/μs Uoc

4 kV, 4 kV

voltage protection level a1–b1, a1 (b1) – PE Up

160 V, 530 V

Maximum current protection

16 A gL/gG or C 16 A

Response time line - line ta

25 ns

Response time line - PE ta

100 ns

Degree of protection

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

Cross-section of connected conductors

Solid max

Stranded max

 

ISO: 4 mm2 ; AWG: 11

ISO: 2,5 mm2 ; AWG: 13

Tightening torque

0,6 Nm

Fault indication

red indicator

Meets the requirements of standard

EN 61643-21

EN 61643-11 + A11 T3

Ordering number

8595090521877


Additional Information:
  • Item Code: DP-012
  • Minimum Order Quantity: 10 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
Save time! Get a Best Deal

*Your information is safe with us.

REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Surge Arresters

DP-024

Surge arrester for low-voltage power supplies Visual fault signaling Designed to protect a line of equipment connected to distributions of DC and AC supply voltage. According to the concept of lightning protection zones, it is installed at the boundary of LPZ 1–LPZ 2 zones and higher.

Technical Data

DP-024

Location SPD

ST 2

Nominal voltage Un

24 V AC/DC

Maximum operating voltage Uc

44 V DC / 22 V AC

Nominal current IL

16 A

C2 nominal discharge current (8/20 μs) per line In

2 kA

C2 voltage protection level line - line at In UP

200 V

C2 voltage protection level line - PE at In Up

530 V

C3 voltage protection level line - line at 1 kV/μs In

2 kA, 2 kA

C3 voltage protection level line - PE at 1 kV/μs Uoc

4 kV, 4 kV

voltage protection level a1–b1, a1 (b1) – PE Up

200 V, 530 V

Maximum current protection

16 A gL/gG or C 16 A

Response time line - line ta

25 ns

Response time line - PE ta

100 ns

Degree of protection

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

Cross-section of connected conductors

Solid max

Stranded max

 

ISO: 4 mm2 ; AWG: 11

ISO: 2,5 mm2 ; AWG: 13

Tightening torque

0,6 Nm

Fault indication

red indicator

Meets the requirements of standard

EN 61643-21

EN 61643-11 + A11 T3

Ordering number

8595090516040

 


Additional Information:
  • Item Code: DP-024
  • Minimum Order Quantity: 10 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Surge Arresters

DP-048

Surge arrester for low-voltage power supplies Visual fault signaling Designed to protect a line of equipment connected to distributions of DC and AC supply voltage. According to the concept of lightning protection zones, it is installed at the boundary of LPZ 1–LPZ 2 zones and higher.

Technical Data

DP-048

Location SPD

ST 2

Nominal voltage Un

48 V AC/DC

Maximum operating voltage Uc

90 V DC / 22 V AC

Nominal current IL

16 A

C2 nominal discharge current (8/20 μs) per line In

2 kA

C2 voltage protection level line - line at In UP

360 V

C2 voltage protection level line - PE at In Up

550 V

C3 voltage protection level line - line at 1 kV/μs In

2 kA, 2 kA

C3 voltage protection level line - PE at 1 kV/μs Uoc

4 kV, 4 kV

voltage protection level a1–b1, a1 (b1) – PE Up

360 V, 550 V

Maximum current protection

16 A gL/gG or C 16 A

Response time line - line ta

25 ns

Response time line - PE ta

100 ns

Degree of protection

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

Cross-section of connected conductors

Solid max

Stranded max

 

ISO: 4 mm2 ; AWG: 11

ISO: 2,5 mm2 ; AWG: 13

Tightening torque

0,6 Nm

Fault indication

red indicator

Meets the requirements of standard

EN 61643-21

EN 61643-11 + A11 T3

Ordering number

8595090521884


Additional Information:
  • Item Code: DP-048
  • Minimum Order Quantity: 10 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Surge Arresters

DP-060

Surge arrester for low-voltage power supplies Visual fault signaling Designed to protect a line of equipment connected to distributions of DC and AC supply voltage. According to the concept of lightning protection zones, it is installed at the boundary of LPZ 1–LPZ 2 zones and higher.

Technical Data

DP-048

Location SPD

ST 2

Nominal voltage Un

60 V AC/DC

Maximum operating voltage Uc

112 V DC / 80 V AC

Nominal current IL

16 A

C2 nominal discharge current (8/20 μs) per line In

2 kA

C2 voltage protection level line - line at In UP

390 V

C2 voltage protection level line - PE at In Up

550 V

C3 voltage protection level line - line at 1 kV/μs In

2 kA, 2 kA

C3 voltage protection level line - PE at 1 kV/μs Uoc

4 kV, 4 kV

voltage protection level a1–b1, a1 (b1) – PE Up

390 V, 550 V

Maximum current protection

16 A gL/gG or C 16 A

Response time line - line ta

25 ns

Response time line - PE ta

100 ns

Degree of protection

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

Cross-section of connected conductors

Solid max

Stranded max

 

ISO: 4 mm2 ; AWG: 11

ISO: 2,5 mm2 ; AWG: 13

Tightening torque

0,6 Nm

Fault indication

red indicator

Meets the requirements of standard

EN 61643-21

EN 61643-11 + A11 T3

Ordering number

8595090521907


Additional Information:
  • Item Code: DP-60
  • Minimum Order Quantity: 10 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
Save time! Get a Best Deal

*Your information is safe with us.

REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Lightning Current Arresters

FLP-7-V/3+1

FLP-7-V/3S+1

SPD type 1 and type 2

 

4-pole (3+NPE) arrester for 3-phase TT (TNS) networks Total Iimp= 25 kA (10/350) Varistor lightning and surge current arresters and heavy duty encapsulated spark gap connected in the mode 3+1. To be installed in low-voltage distributions at the boundary of LPZ 0B and LPZ 1 zones to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version „S“. * Version UC =385 V available on request

Technical data

L-N

N-PE

Nominal voltage Un

230 V AC

-------

Maximum operating voltage Uc

275 V AC

255 V AC

Nominal discharge current (8/20 μs)/pole In

30 kA

30 kA

Maximum discharge current (8/20 μs)/pole Imax

60 kA

60 kA

Lighting impulse current (10/350 μs)/pole Iimp

7 kA

25 kA

Voltage protection level Up

1,2 kV

1,5 kV

Voltage protection level (L - PE) Up

               1,5 kv                                           

 

Response time ta

25 ns

100 ns

Ability to independently switch off the following current If

no following current

100 A

Short-circuit proof at maximum overcurrent protection

50 kArms

-------

Maximum overcurrent protection

160 A gL/gG

--------

Degree of protection

IP 20

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

DIN rail 35 mm

 For Catalouge Kindly Check Attachment.


Additional Information:
  • Item Code: FLP7V3
  • Minimum Order Quantity: 15 Pieces
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Lightning Current Arresters

FLP-7-V/1

FLP-7-V/1 S

SPD type 1 and type 2

versatile single-pole arrester Varistor lightning and surge current arrester to be installed in low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version „S“.* Version UC =385 V available on request

Technical data

FLP-7-V/1 S

Nominal voltage Un

230 V AC

Maximum operating voltage Uc

275 V AC / 350 V DC

Nominal discharge current (8/20 μs) In

30 kA

Maximum discharge current Imax

60 kA

Lightning impulse current (10/350 μs) Iimp

7 kA

Voltage protection level Up

1,2 kV

Response time ta

25 ns

Short-circuit proof at maximum overcurrent protection

50 kArms

Maximum overcurrent protection

160 A gL/gG

Degree of protection

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

Cross-section of connected conductors

Solid min/max

Stranded min/max

 

ISO: 1/35 mm2 ; AWG: 17/2

ISO: 1/25 mm2 ; AWG: 17/4

Fault indication

red indication field

Remote indication – S design

potential-free change-over contact

Remote indication contacts

250 V / 0,5 A AC, 250 V / 0,1 A DC

Cross-section of remote indication conductors

max. 1,5 mm2

Meets the requirements of standard

IEC 61643-11 ed. 1.0 T1T2

EN 61643-11:2012 T1T2

 

Yes! I am Interested
REQUEST CALLBACK
Ask Latest Price

Product Price: Get Latest Price

Lightning Current Arresters

FLP-7-V/1+1

FLP-7-V/1S+1

SPD type 1 and type 2

2-pole (1+NPE) arrester for single phase TT (TNS) networks Varistor lightning and surge current arrester and heavy duty encapsulated spark gap in the mode 1+1. To be installed in low-voltage distributions at the boundary of LPZ 0B and LPZ 1 zones to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version „S“. * Version UC =385 V available on request

 

Technical data

L-N

N-PE

Nominal voltage Un

230 V AC

-------

Maximum operating voltage Uc

275 V AC

255 V AC

Nominal discharge current (8/20 μs) In

30 kA

30 kA

Maximum discharge current (8/20 μs) Imax

60 kA

60 kA

Lighting impulse current (10/350 μs) Iimp

7 kA

25 kA

Voltage protection level Up

1,2 kV

1,5 kV

Voltage protection level (L - PE) Up

                                                        1,5 kV

 

Response time ta

25 ns

25 ns

Ability to independently switch off the following current Ifi

no following current

100 A

Short-circuit proof at maximum overcurrent protection

50 kArms

----------

Maximum overcurrent protection

160 A gL/gG

----------

Degree of protection

IP 20

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

DIN rail 35 mm

For catalouge, Kindly check Attachment.


Additional Information:
  • Minimum Order Quantity: 10 Pieces
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: INDIA
  • Delivery Time: Four Weeks
Yes! I am Interested
View PDF
X
 

Download Brochure
Explore more products
Sabo Systems Pvt. Ltd.

Pawan Agarwal(Director)
Banarsi Complex, Ist Floor Opposite Umrao Theatre, Nishatganj
Lucknow - 226006
Uttar Pradesh, India
Send Email
© Sabo Systems Pvt. Ltd.. All Rights Reserved (Terms of Use)
Developed and Managed by IndiaMART InterMESH Limited